FIRE RESISTANT CABLE, COPPER CONDUCTOR, MICA TAPE, XLPE INSULATED, LSZH SHEATHED (CXH/FR)
PRODUCT OVERVIEW
- Fire resistant cable, copper conductor (Class 2), mica tape, XLPE insulated, LSZH sheathed.
- Fire resistant cables are proper used for public facilities, backup power systems, emergency systems, fire alarm systems, sprinklers, smoke detection and extraction equipment, emergency lighting and evacuation systems…
STANDARD
- TCVN 5935-1 / IEC 60502-1
- TCVN 6612 / IEC 60228
- IEC 60331-21; IEC 60332-1,3
- BS 6387
- IEC 60754-1,2; IEC 61034-2
IDENTIFICATION
- Insulation color: By color tapes
- Multi-core cable:
- 2 cores: Red, without tapes
- 3 cores: Red, yellow, blue
- 4 cores: Red, yellow, blue, without tapes
- Sheath color: Orange color or customer’s requirement
CONSTRUCTION

TECHNICAL CHARACTERISTICS
- Rated voltage Uo/U: 0.6/1 kV
- Maximum conductor temperature for normal operation is 90°C
- Maximum conductor temperature for short-circuit (5 s maximum duration) is 250°C
- Cables are subjected to fire at 950°C for 3 hours and passing BS 6387 Cat. C, W, Z
- The fire resistant cables have a significant reduced tendency to propagate fire
- The cables have low emission of smoke and acid gas when affected by fire
- The cables must self-extinguish after removing the fire source
- Min. bend radius: 8xD (D: Overall diameter of cable)